Process Alarms

Process alarms alert you when the module has exceeded configured high or low
thresholds for each channel. You can latch process alarms. These are set at the
following configurable alarm trigger points:

• High high
• High
• Low
• Low low

The values for each limit are entered in scaled engineering units.

Alarm Deadband

You can configure an alarm deadband to work with the process alarms. The
deadband lets the process alarm status bit remain set, despite the alarm condition
disappearing, as long as the input data remains within the deadband of the
process alarm.

The figure below shows input data that sets each of the alarms at some point
during module operation. In this example, Latching is disabled; therefore, each
alarm turns OFF when the condition that caused it to set returns to normal.

Table 4 - Input Data That Sets Each Of the Alarms

43153

High high

Low low

Low

High

Alarm deadbands

High high alarm turns OFF
High alarm remains ON

High high alarm turns ON
High alarm remains ON

Normal input range

Low low alarms turns OFF
Low alarm remains ON

High alarm turns OFF

Low low alarms turns ON
Low alarm remains ON

Low alarms turns OFF

Low alarms turns ON

High alarm
turns ON