Hart modules used with asset management software, Considerations for asset management systems, Chapter 9 – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 141: Hart modules, Chapter, Introduction

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

141

Chapter

9

HART Modules Used with Asset
Management Software

Introduction

This chapter describes important points about using the ControlLogix HART
analog modules with asset management systems.

These topics are discussed in this chapter.

Considerations for Asset
Management Systems

The following must be considered before using the I/O modules with
asset management systems, such as FactoryTalk AssetCentre or
Endress+Hauser FieldCare systems.

• HART must be enabled before any asset management system access is

possible, including scanning for multiplexors, if supported by your asset
management software. You do not need to include HART PV or HART
by Channel data in your input tag, but you do need to check the Enable
HART box on the Configuration tab of the Module Properties dialog box.

• The Logix controller must be connected to the I/O module. If the Logix

controller is not connected, the module configuration was not sent to the
HART module, and the channel is not yet configured for HART access.

• If using a handheld HART communicator and configuration tool, such as

Rosemount 275 or Meriam, configure the tool as the secondary master.
The Meriam handheld has a high-speed mode, which assumes it is the only
master present. In this mode, the handheld may conflict with the I/O
module. Usually, the Meriam handheld automatically detects the proper
setting, but if not, set it manually.

• The ConfigurationChanged indication in the Field Device Status is

automatically reset by the I/O module. Asset management systems might
miss this indication if they are offline at the time of a change.

• A separate configuration-changed indication is in the field device status for

the primary master (1756-IF8H or 1756-IF16H module) and secondary
master (handheld, for example). The I/O modules do not reset the
secondary master configuration changed status.

HART traffic from asset management pass-through messages or from secondary
masters slows the update rate of HART data in the controller or other
pass-through message clients. In the 1756-IF8H or 1756-OF8H modules,
extra traffic on one channel also affects other channels.

Topic

Page

Considerations for Asset Management Systems

141