Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

133

Getting HART Data By Using CIP MSG Chapter 8

HART Module Scanning
Diagram with Pass-through
Messages

When HART pass-through messages are being sent, the normal data acquisition
sequence is modified as shown in the diagram. In this case, the Pass-through is
configured to send one pass-through message for each channel scanned.

It can be configured for lower priority on the Configuration tab of the
Module Properties dialog box.

Yes

Update Input Tag

Device in
Scan List?

Send Command
3 or 9 to Read
Dynamic
Process Variable

Reply?

Read Configuration
Information, Such as
Tag, Units, Range

Put Device in Scan List

Send Command 0
Read Unique Identifier

New
Configuration
Indicated?

Remove
Device from
Scan List

Read
Configuration
Information,
Such As Tag,
Units, Range

Signal Configuration
Changed in Input Tag

Go To First Channel

Next Channel

Last
Channel?

No

Signal Configuration
Changed in Input Tag

Yes

Reply?

Yes

No

Yes

Process 1 Pass-
through Message

No

No

No

Yes