1756-if8h module fault and status reporting – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 63

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

63

1756-IF8H HART Analog Input Module Chapter 4

Figure 10 - Simplified 1756-IF8H Voltage Input Circuit

1756-IF8H Module Fault and
Status Reporting

The 1756-IF8H module multicasts status/fault data to the controller with its
channel data. The fault data is arranged to let you choose the level of granularity
you desire for examining fault conditions. Three levels of tags work together to
provide an increasing degree of detail as to the specific cause of faults on the
module.

Table 6

lists tags you can examine in ladder logic to indicate when a fault has

occurred.

0.01

μF

Analog to
Digital
Converter

22 K

Ω

10 M

Ω

-15 V

+

-

0.01

μF

22 K

Ω

10 M

Ω

249

Ω

1/4 Watt

INO+

I RTN-O

INO-

+15 V

Differential
Voltage
Inputs

V

+

-

RTN

RTN

RTN

RTN

Table 6 - Tags That Can Be Examined in Ladder Logic

Tag

Description

Tag Name
Analog and HART PV

Tag Name
Analog and HART by Channel

(1)

Module Fault Word

This word provides fault summary reporting.

ModuleFaults

ModuleFaults

Channel Fault Word

This word provides underrange, overrange, and
communication fault reporting.

ChannelFaults
ChxFault

ChannelFaults
ChxFault

Channel Status Word

These words provide individual channel underrange
and overrange fault indications and reporting for
process alarms, rate alarms, and calibration faults.

ChxStatus

Chx.DeviceStatus
Chx.DeviceStatus.AlarmStatus

HART Faults

This provides HART communication status.

HARTFaults, ChxHARTFault Chx.DeviceStatus.HARTFault

HART Device Status

This provides HART field device health.

HART.ChxDevice Status

Chx.DeviceStatus.FieldDeviceStatus

(1) Available only for 1756-IF8H firmware revision 2.1.