1756-OF8H HART Analog Output Module

Data Formats

Data format determines which values are included in the Input tag of the module
and the features that are available to your application. Select the data format on
the General tab in RSLogix 5000 software. The following data formats are
available for the 1756-IF8H module.

• Choose Analog and HART PV if you prefer the members of your tag to be

arranged similar to non-HART analog input modules, with the analog
values for all channels grouped together near the end of the tag. This makes
it easy to view all eight analog values at once.

• Choose Analog and HART by Channel if you prefer Status, Analog Value,

and Device Status for each channel to be together in the tag. This makes it
easier to view all of the data related to one field device.

Resolution

The output module is capable of 15 or 16 bit resolution.

Description

Analog
signal
values

Analog
status

HART secondary
process variables
and device health

HART and Analog data
for each channel
grouped together in tag

Format

Analog Only

X

X

Analog and HART
PV

X

X

X

Analog and HART
by Channel

(1)

(1) Available only for 1756-OF8H firmware revision 2.1.

X

X

X

X

Number of
Significant Bits

Range

Resolution

16 bits

+/- 10.4V

320

μV

15 bits

0…20 mA
4…20 mA

0.65

μA