Appendix A Tag Definitions

Analog and HART by Channel

Table 61 - Analog and HART by Channel (AB:1756-IF8H_AnalogHARTbyChannel:I:0)

Member Name

Type

Style

Description

ChannelFaults
(Ch0…Ch7)

INT

Binary

Indicates a problem with analog data on Channel x or broken communication between the Logix
controller and the 1756-IF8H module.
Example: Set if analog signal is larger than 20 mA.

ChxFault

BOOL

ChannelFaults.x

ModuleFaults

SINT

Binary

CalFault

BOOL

Decimal

ModuleFaults.1, 1756-IF8H module calibration failed.

Calibrating

BOOL

Decimal

ModuleFaults.2, Calibration in progress.

UpdatedStatusReady

BOOL

Decimal

ModuleFaults.3, Module has collected updated Additional Device Status from HART command 48.
This status can be retrieved by using the Read Additional Status service, 16#4C. For more
information about this service, see

Read Additional Status (Service Code = 16#4C) on page 125

.

AnalogGroupFault

BOOL

Decimal

ModuleFaults.7, Indicates a fault has occurred on any channel (any of ChannelFaults).

Ch0

AB:1756_IF8H_HARTDataAll_Struct:I:0, Channel 0 analog and HART data.

Data

REAL

Float

Analog value in engineering units.

DeviceStatus

AB:1756_IF8H_HARTStatusAll_Struct:I:0, Channel 0 HART Device status info.

HARTInit

BOOL

Decimal

Searching for or Initializing HART device.
If this is 0 and Fail is 1, then HART is not Enabled on this channel.
If both are 1, then 1756-IF8H is sending out HART messages attempting to establish
communication with a HART device.

HARTCommFail

BOOL

Decimal

HART communication failure or device not found or HART not enabled.
If this bit is 1, none of the other data in the HART part of the Input Tag are valid.
(HART.PVStatus will be set to 0 to also indicate this)

MsgReady

BOOL

Decimal

Pass-through message reply is ready for query service.

CurrentFault

BOOL

Decimal

Analog current measurement does not match the current the Field Device reported over
the HART network.

ConfigurationChanged

BOOL

Decimal

The field device configuration has changed and new field device configuration information can be
obtained from the 1756-IF8H module via CIP MSG GetDeviceInfo, which will clear this bit.

BrokenWire

BOOL

Decimal

Indicates that current is not flowing through the module as expected. This might be caused by
broken wiring, RTB removal, or a powered-off field device.

HARTFault

BOOL

Decimal

Indicates a problem with HART data from the field device on Channel x.
Examples are HART not enabled, HART device not connected, HART communication failure
due to noise.
The following Field Device Status conditions also cause this to be set: Device Malfunction,
PV Out of Limits, Loop Current Saturated, and Loop Current Fixed.

ResponseCode

SINT

Binary

HART communication status byte or Response code from a recent HART reply. See

Response Code

and Field Device Status on page 195

for more information.

FieldDeviceStatus

SINT

Binary

HART device status byte from a recent HART reply. Indicates the health of the HART Field device.
See

Field Device Status Bit Mask Definitions on page 196

for more information.

PVOutOfLimits

BOOL

Decimal

The primary variable is beyond its operating limit.

VariableOutOfLimits

BOOL

Decimal

A device variable not mapped to the PV is beyond its operating limits.

CurrentSaturated

BOOL

Decimal

The loop current has reached its upper or lower endpoint limit and cannot increase or decrease
any further.

CurrentFixed

BOOL

Decimal

The loop current is being held at a fixed value and is not responding to process variations.

MoreStatus

BOOL

Decimal

More status information is available via command 48, ‘Read Additional Status’ information.

ColdStart

BOOL

Decimal

A power failure or device reset occurred.