Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

91

Configure the Modules with RSLogix 5000 Software Chapter 7

General Tab

Complete the se instructions for a general configuration.

1.

On the General tab, do these steps:
a. Type a name for the module.
b. Type an optional description for the module.
c. Select the slot number for the module.

2.

On the Module Definition box, click Change.

The Module Definition dialog box appears.

3.

Complete these actions:

Parameter

Action

Values

Series

Displays the series letter that matches your
module’s series

N/A

Revision

Choose the revision number that matches the label on the
side of your module, be sure that the minor revision
number also matches

N/A

Electronic Keying

Choose the electronic keying method
See

Electronic Keying on page 17

for more information

Exact Match
Compatible Module (default)
Disable Keying

Connection

Choose the connection type

Data - has more tabs on the Module Properties dialog box

than Listen-only because of configuration settings for
alarms, calibration

Listen-only - has no configuration data, does not send output

data (1756-OF8H module)
See

Listen-only Mode on page 49

for more information.

Input Data

Choose the input data mode

Analog Only
Analog and HART PV
Analog and HART by Channel (available only for

firmware revision 2.1)

See

HART Configuration

for more information.

Coordinated System Time

Not configurable

Timestamped

Data Format

Not configurable

Float