Rockwell Automation 1771-IFE ANALOG INPUT MODULE User Manual
Page 16
![background image](/manuals/579632/16/background.png)
2–4
Installing the Input Module
Publication 1771Ć6.5.115 - February 1999
Selection
Plugs
10950ĆI
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Reposition the configuration plugs associated with each
input channel according to your requirements.
You can mix voltage mode and current mode
settings on the module. Make sure that the
entire module is set for either singleĆended or
differential. Do not mix them.
2
Voltage Mode
Differential Current SingleĆended Current
Differential or SingleĆended (factory set)
Current Mode
Channel
1 and 2
Channel
3 and 4
Channel
5 and 6
Channel
7 and 8
Channel
9 and 10
Channel
11 and 12
Channel
13 and 14
Channel
15 and 16
Differential
SingleĆended
Odd channel current
Even channel voltage
Even channel current
Odd channel voltage
SingleĆended
Reposition the cover and secure with
the fours screws removed in step 1.
19813
13