The module is shipped with the series A/B simulation jumper set in
position

POS G for Series C applications. This setting returns input

data above and below the range end points. If you are replacing a
Series A or B 1771-IFE module with this module, and your
application cannot tolerate underrange/overrange data, reset the
simulation jumper to the

POS E position as shown below, to

internally limit input data to range end points.

POS G

POS E

Simulation Jumper (shown in POS E position

for series A and B simulation)

Top edge of circuit board

1. Locatethesimulation jumper at thetop edge

of themodulecircuit board.

2. Using your fingers, slidethejumper off the2 posts.
3. Carefully position the jumper on 2 of the 3 posts that

correspond to your requirement.

Set the Series A/B Simulation Jumper

A/B

Simulation

Jumper

POS G

POS E

Simulation Jumper (shown in POS G position

for series C )

Top edge of circuit board

Series A and B

Simulation

Series C

Application

Setting the Series A/B

Simulation Jumper