![background image](/manuals/579632/53/background.png)
Off
On
Legend
Blinking
7–3
Troubleshooting Your Input Module
Publication 1771Ć6.5.115 - February 1999
The following table lists the probable cause and recommended
actions for some common trouble indications.
Troubleshooting Chart for Analog Input Module (1771-IFE/C)
Indicators
Probable Cause
Recommended Action
RUN (green)
FLT (red)
Normal operation
None
RUN (blinking)
FLT (off)
Awaiting configuration Block Transfer
Write
Send configuration BTW
RUN (green)
FLT (red)
Hardwarefailurein module
Return module for repair
RUN
Neither LED
FLT
comes on
No power
Turn off power. Remove and reinsert
module into chassis. Return power.
If problem still exists, and chassis power
supply is functioning properly, return the
modulefor repair.