Rockwell Automation 1771-IFE ANALOG INPUT MODULE User Manual

Page 53

Advertising
background image

Off
On

Legend

Blinking

7–3

Troubleshooting Your Input Module

Publication 1771Ć6.5.115 - February 1999

The following table lists the probable cause and recommended
actions for some common trouble indications.

Troubleshooting Chart for Analog Input Module (1771-IFE/C)

Indicators

Probable Cause

Recommended Action

RUN (green)

FLT (red)

Normal operation

None

RUN (blinking)

FLT (off)

Awaiting configuration Block Transfer

Write

Send configuration BTW

RUN (green)

FLT (red)

Hardwarefailurein module

Return module for repair

RUN

Neither LED

FLT

comes on

No power

Turn off power. Remove and reinsert

module into chassis. Return power.

If problem still exists, and chassis power

supply is functioning properly, return the

modulefor repair.

Advertising