Appendix

B

Publication 1771Ć6.5.115 - February 1999

Differences Between Series A

and B Modules and Series C

Modules

The following is a list of the major differences between the Series A
and B 1771-IFE modules and the series C 1771-IFE module

Figure B.1

Differences Between 1771ĆIFE Series A and B and 1771ĆIFE

Series C Modules

Feature

Series A, and B

Series C

Indicator lights

1. At power-up, the green run indicator

comes on and stays on.

2. Limited to 3 bits of diagnostic

information

1. At powerup, the green run indicator blinks until a

configuration BTW is received. After a configuration BTW

is received, the green indicator stay on.

2. Has 6 bits of diagnostic information representing 6

possible faults.

Input Data

Input clamped at range ends. Will not go

above or below range limits.

Returns input data above and below the range end points. For

example, a 1-5V input with default scaling will return all values

between +5.2V. Jumper settable for Series A and B simulation

to internally limit input to range end points.

Default Scaling

Allows default scaling with both maximum and minimum

scaling values as zero. No scaling error will be reported.

Block Transfer Lengths

Maximum block transfers lengths of 20

words for BTR and 37 words for BTW.

Default length of 0 words.

Maximum block transfers lengths of 22 words for BTR and 39

words for BTW (due to autocalibration). Default length of 0

words (same as series A).

Configuration Plugs

24 configuration plugs to set on 3 row

headers.

16 configuration plugs to set on eight 2 row headers.

Compatibility

The series A and B modules are compatible

with the 1771ĆAL PLC local adapter.

The series C module is not compatible with the 1771ĆAL PLC

local adapter.

Calibration Procedures

Used jumpers and potentiometers to adjust

10V reference and null input offset.

Uses precision voltage source to supply voltage and a block

transfer to set offset and gain.

Agency Approvals

Series A module not CE certified. Series B

module CE certified.

Series C module CE certified.