Input range selection – Rockwell Automation 1771-IFE ANALOG INPUT MODULE User Manual

Page 34

Advertising
background image

4–2

Configuring Your Module

Publication 1771Ć6.5.115 - February 1999

During normal operation the processor transfers 1 to 39 words to the
module when you program a block transfer write instruction to the
module’s address. This BTW file contains configuration words, and
calibration words (words 38 and 39) for each channel.

When a block transfer transfer length of 0 is programmed, the
1771-IFE/C will respond with the series A default length of 37.

You can configure the module to operate with any of five voltage or
three current ranges. You select individual channel ranges using the
designated words of the block transfer write instruction (Table 4.A).
Use BTW word 1 for range selection of channels 1 through 8, and
BTW word 2 for channels 9 through 16. Two bits are allocated for
each channel.

Table 4.A Input Range Selection Bits

Bit 01

Bit 00

Voltage or current input

0

0

1 to 5V dc, 4 to 20mA

1

0

1

0 to 5V dc, 0 to 20mA

1

1

0

Ć5 to +5V dc, Ć20 to +20mA

1,2

1

1

Ć10 to +10V dc

2

, 0 to 10V dc

1

Current input mode selected by configuration plug.

2

Configurable using biĆpolar scaling.

Dec. Bits

15 14 13 12

11

10 09

08

07 06 05 04 03 02 01 00

Description

Octal Bits

17 16 15 14

13

12 11

10

07 06 05 04 03 02 01 00

Description

Write Word 1

8

7

6

5

4

3

2

1

Range Selection Ć Channels 1 thru 8

Write Word 2

16

15

14

13

12

11

10

9

Range Selection Ć Channels 9 thru 16

Table 4.B shows the incremented voltage or current assigned to each
bit for the seven different input ranges. For example, if the channel
1 input range is 0 to +5V and the actual incoming signal is at
mid-range (+2.5V) the value in the module’s data word would be
0000 1000 0000 0000 (binary) or 2048 (decimal). The input is
2048/4096, or 1/2 of full scale.