Default configuration – Rockwell Automation 1771-IFE ANALOG INPUT MODULE User Manual

Page 40

Advertising
background image

4–8

Configuring Your Module

Publication 1771Ć6.5.115 - February 1999

If a write block of five words, with all zeroes, is sent to the Analog
Input Module (cat. no. 1771-IFE series C), default selections will be:

1 to 5V dc or 4 to 20mA (dependent on configuration jumper
setting)

BCD data format

no real time sampling (RTS)

no filtering

no scaling

single-ended inputs

Table4.G

Analog Input Module(1771ĆIFE/C) Block Transfer Write

Configuration Block

Dec. Bits

15 14 13 12

11

10 09

08

07 06 05 04 03 02 01 00

Description

Octal Bits

17 16 15 14

13

12 11

10

07 06 05 04 03 02 01 00

Description

Word 1

8

7

6

5

4

3

2

1

Range Selection Ć Channels 1 thru 8

2

16

15

14

13

12

11

10

9

Range Selection Ć Channels 9 thru 16

3

Real Time Sampling

Data

Format

Input

Type

Digital Filter

Real time sampling, data format, input

type and digital filter

4

16 15 14 13

12

11 10

9

8

7

6

5

4

3

2

1 Sign Bits, minimum scaling values

5

16 15 14 13

12

11 10

9

8

7

6

5

4

3

2

1 Sign Bits, maximum scaling values

6

Channel 1 Ć minimum scaling

7

Channel 1 Ć maximum scaling

8

Channel 2 Ć minimum scaling

9

Channel 2 Ć maximum scaling

10

Channel 3 Ć minimum scaling

37

Channel 16 Ć maximum scaling

38

16 15 14 13

12

11 10

9

8

7

6

5

4

3

2

1 Offset Calibration

39

16 15 14 13

12

11 10

9

8

7

6

5

4

3

2

1 Gain Calibration

Default Configuration