3–6

Module Programming

Publication 1771Ć6.5.115 - February 1999

Figure 3.4

Block Transfer Time

1

2

3

4

5

6

7

8

9

10

Endof block

transfer write

1st

Scan

Module available to perform block transfer.

Block transfers are inhibiteduntil any

programmedRTS time has elapsed.

Note: Configure/Calibration time:

SingleĆended mode = 2s configure; 4.5s calibration

Differential mode = 1s configure; 2.5s calibration

Scan time:

= 13.7ms for 8 differential inputs (no scaling or digital filter);

= 27.4ms for 16 singleĆended inputs (no scaling or digital filter)

12689

2nd

Scan

3rd

Scan

Block

Transfer

Write

time

Configure

time

Calibration

time

See note

In this chapter, you learned how to program your programmable
controller. You were given sample programs for your PLC-2, PLC-3
and PLC-5 family processors.

You also read about module scan time.

Chapter Summary