Rockwell Automation 1771-IFE ANALOG INPUT MODULE User Manual

Page 39

Advertising
background image

4–7

Configuring Your Module

Publication 1771Ć6.5.115 - February 1999

Important: Scaling values must always be entered in BCD

format, even if the data format chosen is binary. If
scaling is selected for any channel, all channels must be
scaled. If scaling is not required on certain channels,
set those to the default input range: 0 to 4095 for 0 to +
voltage or current ranges, and -4095 to +4095 for - to +
voltage or current ranges.

If scaling is not selected, the module requires specific minimum
BTR file lengths for the number of channels used.
The BTW file
length can be set to 3 words. Table 4.F shows the required BTW and
BTR file lengths.

Table 4.F

Block Transfer Read and Write File Lengths

Channels

Used

BTR File

Length

BTW File

Length

1

5

7

2

6

9

3

7

11

4

8

13

5

9

15

6

10

17

7

11

19

8

12

21

9

13

23

10

14

25

11

15

27

12

16

29

13

17

31

14

18

33

15

19

35

16

20

37

Calibration

21

38

Words

22

39

Important: Use decimally addressed bit locations for PLC-5

processors.

The module will return values outside the scaling range. For
example, if a module is in the 0–5V dc mode, scaled for 0 to 5000,
and has –2V dc applied, it will return –2000.