Troubleshooting a bad input – Rockwell Automation 1771-IFE ANALOG INPUT MODULE User Manual

Page 58

Advertising
background image

7–8

Troubleshooting Your Input Module

Publication 1771Ć6.5.115 - February 1999

A noise spike which exceeds +14.25V on an input will also cause
crosstalk to occur. This transient condition will affect all inputs.
Refer to publication 1770-4.1, “Wiring and Grounding Guidelines
for Noise Immunity.”

After determining that the module is operating correctly,
troubleshoot any faulty inputs by:

measuring each input with respect to module common

disconnecting inputs from the field wiring arm one at a time
while observing module action

testing for input channel functionality

Measuring Each Input with Respect to Module Common

During this procedure, monitor the input data table of the
programmable controller and observe any changes which occur.

1. Make sure the field wiring arm is in position on the module.

2. Apply power to the 1771 I/O chassis.

3. Check each input (either single-ended or differential) for common

mode voltages exceeding +14.25V with respect to module
common.

A. Hold the positive probe of the voltmeter on the first input

terminal.

B. Hold the negative probe of the voltmeter on a module

common terminal (terminals 20 or 21).

4. If any voltage is seen that exceeds +14.25V, remove that

channel’s input wiring and observe the affect on the input data
table of the programmable controller.

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing input wiring.

Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.

Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.

If no other common mode voltages are present, the input data for
all other channels should stabilize to some predictable value.

More

Troubleshooting a Bad

Input

Advertising