7–4

Troubleshooting Your Input Module

Publication 1771Ć6.5.115 - February 1999

The following allows you to run a check on module operation, and
isolate a fault either to the module or external to the module.

Connect the Module in a Simple Test System

Set up a 1771 I/O chassis with a PLC-5 processor in the leftmost
slot.

4

5

Switches

Addressing

Pressed in

on right ON (closed)

Pressed in

on left OFF (open)

Always Off

2Ćslot
1Ćslot
1/2 slot

Off

Off

Set the chassis backplane switch 5 to ON. All other backplane switches to Off.

This sets the chassis to 1Ćslot addressing.

1

Note: Check the processor screen to verify that the processor is set for 1Ćslot addressing.

OFF

ON

OFF

ON
OFF

OFF

OFF

OFF

Always Off

Place the module in the card guides on the top and bottom of the first slot next to the

processor. These slots guide the 1771ĆIFE/C module into position.

Important: Apply firm even pressure on the module to seat it into its backplane connector.

Swing the chassis locking bar down into place to secure

the modules. Make sure the locking pins engage.

1771ĆA1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis

1771ĆA1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis

locking tab

card guides

IFE module

IFE module

19809

card guides

locking bar

locking bar pin

Snap the chassis latch over

the top of the module to secure it.

2

After inserting the module into the slot, apply power to the chassis.

PLCĆ5 Processor

PLCĆ5 Processor

CheckingModule

Operation