Block Transfer (Mini-PLC-2 and PLC-2/20 Processors)

Publication 1771Ć6.5.115 - February 1999

The input module transfers a specific number of words in one block
length. The number of words transferred is determined by the block
length entered in the output image table control byte corresponding
to the module’s address.

The bits in the output image table control byte (bits 00 - 05) must be
programmed to specify a binary value equal to the number of words
to be transferred.

For example, Figure E.2 shows if your input module is set up to
transfer 6 words, you would set bits 01 and 02 of the lower image
table control byte. The binary equivalent of 6 words is 000110. You
would also set bit 07 when programming the module for block
transfer read operations. Bit 06 is used when block transfer write
operations are required.

Figure E.2 Setting Block Length(Multiple GET Instructions

only)

1 0 0 0 0 1 1 0

Data Address

Contains Module

Address in BCD

Output ImageTableControl

ByteContains Read

EnableBit and Block

Length in Binary Code

010

012

017

027
030

1

2

0

Data Table

1
R

Control

Byte

Read 6 Words

from Module

Block Transfer

Read Enable Bit

For Block

Transfer Active

Operations Only

Output ImageTable

12172

Number of

Words to

T

f

Binary Bit Pattern

Lower Output Image Table Byte

Transfer

05

04

03

02

01

00

Default

0

0

0

0

0

0

1

0

0

0

0

0

1

2

0

0

0

0

1

0

3

0

0

0

0

1

1

4

0

0

0

1

0

0

5

0

0

0

1

0

1

6

0

0

0

1

1

0

:

:

18

0

1

0

0

1

0

19

0

1

0

0

1

1

Setting the Block Length

(Multiple GET Instructions

only)