Chapter

5

Publication 1771Ć6.5.115 - February 1999

Module Status and Input Data

In this chapter, we describe:

reading data from your module

block transfer read block format

Block transfer read programming moves status and data from the
input module to the processor’s data table in one I/O scan
(Figure 5.1). The processor’s user program initiates the request to
transfer data from the input module to the processor.

Figure 5.1

WordAssignments for Analog Input Module (1771ĆIFE/C) Block Transfer Read

Dec. Bits

15 14 13 12 11 10 09 08 07 06 05 04

03

02

01

00

Description

Octal Bits

17 16 15 14 13 12 11 10 07 06 05 04

03

02

01

00

Description

Word 1

HF EE CS RTS IS OR PU

Diagnostics

2

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data underrange for channels 1-16

1

3

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data overrange for channels 1-16

1

4

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data polarity for channels 1-16

5

Channel 1 Input

Channel 1 Input

6

Channel 2 Input

Channel 2 Input

7

Channel 3 Input

Channel 3 Input

8

Channel 4 Input

Channel 4 Input

20

Channel 16 Input

Channel 16 Input

21

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Offset Calibration Results

22

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Gain Calibration Results

Where:

PU= Power up bit

OR = Out of range bit

IS = Invalid scaling bit

RTS = Real time sampling bit

HF = Hardware Fault

EE = EEPROM status bits

CS = Calibration status bits

1

These bits are set (1) at approximately the input range limits selected (Table 5.B).

During normal operation, the processor transfers up to 20 words (22
during calibration) to the module when you program a BTR
instruction to the module’s address.

When a BTR length of 0 is programmed, the 1771-IFE/C will
respond with the series A module default length of 20.

Chapter Objectives