Example 3 - block transfers, Example 3 - block transfers -10 – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual

Page 102

Advertising
background image

Publication 1746-UM002B-EN-P - August 2004

6-10 Application Examples

Data Table for N10 File (hexidecimal)

Data Table for N11 File (decimal)

Example 3 - Block Transfers

In this example, the module is set up in Class 1, Mode 3 using two
counters. This example uses indirect addressing and block transfers
with a PLC-5 scanner.

Three rungs are added to ladder file 8, the HSCE2 routine:

1. Repeating block transfer writes (BTW) to send eight words of

data to the remote 1746-HSCE2 module.

2. Repeating block transfer reads (BTR) to read eight words of data

from the remote 1746-HSCE2 module.

3. A rung to latch the first BTR done bit when it was satisfactory to

start the 1746-HSCE2 initialization (ladder file 9).

The 1746-HSCE2 initialization routine (ladder file 9) is nearly the same
as the local examples (examples 1 and 2), except the I/O image

Programming Blocks

Offset

0

1

2

3

4

5

6

7

8

9

Module Setup

N10:0

1

101

8

0

0

0

0

0

0

0

Counter Configuration

N10:10

302

C

0

C

0

0

0

0

0

0

Min/Max Count Value Counter 1 N10:20

4

0

0

2

30

0

0

0

0

0

Min/Max Count Value Counter 2 N10:30

104

0

0

7

C8

0

0

0

0

0

Min/Max Rate Value

N10:40

8

FF9C

0

64

0

0

0

0

0

0

Program Ranges

N10:50

410

1

0

0

4

3E7

1

0

0

0

Program Ranges

N10:60

410

2

5

0

9

3E7

2

0

0

0

Program Ranges

N10:70

410

4

A

0

E

3E7

1

0

0

0

Program Ranges

N10:80

410

8

F

0

13

3E7

2

0

0

0

Program Ranges

N10:90

410

10

14

0

18

3E7

1

0

0

0

Program Ranges

N10:100

410

20

19

0

1D

3E7

2

0

0

0

Program Ranges

N10:110

410

40

1E

0

22

3E7

1

0

0

0

Program Ranges

N10:120

410

80

23

0

27

3E7

2

0

0

0

Program Ranges

N10:130

110

100

0

0

1

31F

4

0

0

0

Program Ranges

N10:140

110

200

1

320

3

257

8

0

0

0

Program Ranges

N10:150

110

400

3

258

5

18F

4

0

0

0

Program Ranges

N10:160

110

800

5

190

7

C7

8

0

0

0

Counter Control

N10:170

80

8001

8001

0

0

FF00

FFF

0

0

0

Offset

0

1

2

3

4

5

6

7

8

9

N11:0

170

170

17