Ladder file 8 continued – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual
Page 104

Publication 1746-UM002B-EN-P - August 2004
6-12 Application Examples
Ladder File 8 Continued
0001
BT20:1
EN
EN
DN
ER
BTW
Block Transfer Write
Module Type Generic Block Transfer
Rack
001
Group
0
Module
0
Control Block
BT20:1
Data File
N12:10
Length
8
Continuous
No
0002
BT20:0
EN
BTR_TRIGGER
EN
DN
ER
BTR
Block Transfer Read
Module Type Generic Block Transfer
Rack
001
Group
0
Module
0
Control Block
BT20:0
Data File
N12:0
Length
8
Continuous
No
0003
BT20:0
DN
BTR_DONE
L
B3:0
3
1ST_BTR_DONE
0004
B3:0
3
1ST_BTR_DONE
B3:0
0
HSCE2_INIT_DONE
B3:0
1
HSCE2_ERROR
JSR
Jump To Subroutine
Prog File Number
U:9
INITIALIZE_HSCE2
0005
END
Continuously re-trigger 8-word block transfers to the remote HSCE2.
Continuously re-trigger 8-word block transfers to the remote HSCE2.
Prior to running the HSCE2 configuration hand-shaking (ladder file 9), finish the first BTR.
Jump to the HSCE2 initialization subroutine if: