2-2 Module Operation

Input Configurations

Input configurations determine how the A and B inputs cause the
counter to increment or decrement. The six available configurations
are:

• Pulse/External Direction
• Pulse/Internal Direction
• Up and Down Pulses
• X1 Quadrature Encoder
• X2 Quadrature Encoder
• X4 Quadrature Encoder

See the Summary of Available Counter Configurations on page 2-8 for
the input configurations available for the counters, based on operating
mode.

Pulse/External Direction

With this configuration, the B input controls the direction of the
counter, as shown below. If the B input is low (0), the counter
increments on the rising edges of input A. If the input B is high (1),
the counter decrements on the rising edges of input A.

Figure 2.2 Pulse/External Direction Configuration

1

2

3

2

1

0

1

2

Input A

Encoder or Sensor

Count Pulse

Count Pulse

Count

Input B

Input Z

Direction Control

Sensor or Switch

Direction Control
High = Decrement
Low = Increment