E - comparing 1746-hsce2 to 1746-hsce, Appendix e, Comparing 1746-hsce2 to 1746-hsce – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual

Page 131: Appendix

Advertising
background image

1

Publication 1746-UM002B-EN-P - August 2004

Appendix

E

Comparing 1746-HSCE2 to 1746-HSCE

1746-HSCE

High Speed Counter

1746-HSCE2

Multi-Channel High Speed Counter

Number of Counters

1

2 to 4

Counter Capability

16-bit (±32,767)

24-bit (±8,388,607)

Operating Class

Class 3 only.

Class 1 or Class 4.

Input Voltage

2.8 to 5.5V dc

4.2 to 30V dc

Output Current

0.125 A

1.0 A

Input Frequency
Response

50K Hz

1M Hz

Backplane Response
Time

60 ms

0.7 to 1.6 ms

Module Compatibility

Uses M-files.

Not compatible with SLC5/01 and 5/02

or 1747-ASB.

Supports handshaking.

Compatible with SLC 5/01 and 5/02

and 1747-ASB.

(1)

Rate Periods

Programmable.

Self-determined.

Sequence Mode

24-step

n/a

Count/Rate Modes

12 ranges

16 ranges

Preset Inputs

Multiple preset inputs for 1 counter.

Hard preset disable.

1 preset input for counters 1 and 2 only.

No preset input for counters 3 and 4.

No hard preset disable.

(1) In Class 1 only.