3-10 Installation and Wiring

Single-Ended Wiring (Discrete Devices)

Figure 3.9 Discrete Device Wiring

(1) Calculate the value of the pull-up resistor (R), as shown below:

For 5V dc jumper position:

For 24V dc jumper position:

where:R = pull-up resistor value

Vcc = power supply voltage
Vmin = 4.2 V dc
Imin = 6.3 mA

Power Supply Voltage (Vcc)

Pull-up Resistor Value (R)

5V dc

127

12V dc

238

24V dc

2140

VS

A1(+)

A1(–)

B1(+)

B1(–)

Z1(+)

Z1(–)

+VDC

COM

VS

OUT

COM

OUT

COM

VS

OUT

COM

R

(1)

Power
Supply

Module Inputs

Solid-State
Switch

Proximity Sensor

Photo-electric Sensor
with Open Collector
Sinking Output

R

Vcc

Vmin

(

)

Imin

--------------------------------------

=

R

Vcc

Vmin

(

)

Imin

--------------------------------------

1K

=