Configuration and Programming 4-11

Figure 4.5 Counter Configuration Block Format

Programming Block Identification Bit

(Word 0, Bit 01)

This bit identifies the type of block.

TRMT: Transmit Bit

(Word 0, Bit 15)

A 0 to 1 transition starts a programming cycle.

DEBUG: Debug Mode Selection Bit

(Word 0, Bit 12)

When this bit is set, the debug mode is activated. Debug mode returns
the input data file showing current settings in the counter
configuration block. See Debug Mode Operation on page 5-7.

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Word 0

TRMT

0

0

DEBUG

PGM4

PGM3

PGM2

PGM1

0

0

0

0

0

0

1

0

Word 1

0

0

0

0

0

0

0

0

0

G/P Mode

Input Config

CT

ype

Counter 1

Word 2

RESERVED: Must equal 0

Word 3

0

0

0

0

0

0

0

0

0

G/P Mode

Input Config

CT

ype

Counter 2

Word 4

RESERVED: Must equal 0

Word 5

0

0

0

0

0

0

G/Pmode

CT

ype

0

0

0

0

0

0

G/Pmode

CT

ype

Counter 3 or 4

as indicated

Counter 4

Counter 3

Word 6

RESERVED: Must equal 0

Word 7

RESERVED: Must equal 0