Throughput and timing, On-state current derating – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual
Page 121

Publication 1746-UM002B-EN-P - August 2004
Specifications A-3
On-State Current Derating
Throughput and Timing
2.0 A
1.5 A
1.0 A
0.5 A
20˚C
0˚C
40˚C
60˚C
Temperature
Ma
ximu
m On
-St
ate
Cur
re
nt
(p
er
m
od
ul
e)
Operation
Description
Timing (µs)
Minimum
Typical
Maximum
Throughput
The delay between the time the module receives a pulse and when
its real outputs and the SLC backplane are updated (based on a
count range).
300
700
1600
Input File Update
Time
The delay between the time the module receives a pulse and when
the backplane count value is updated, including setting the I/O
interrupt.
300
600
1500
Output Turn-on
Time
The time it takes for the real output to reach 90% output voltage
after commanded by the module, not including SLC scan time.
–
–
10
Output Turn-off
Time
The time it takes for the real output to reach 10% output voltage
after commanded by the module, not including SLC scan time.
–
–
100
Inductive Turn-off
Time
The time between the module receiving an input pulse and breaking
contact in a BULLETIN 110 contactor.
–
–
50
Rate Accuracy
The accuracy of the reported rate as compared to actual input rate in
the equation: reported rate/actual input rate.
–
0.005%
0.015%