Publication 1746-UM002B-EN-P - August 2004

Installation and Wiring 3-3

Figure 3.1 Jumper Settings

The 5V dc settings respond to inputs with an active voltage between
4.2 and 12 volts. The 24V dc settings respond to inputs with active or
high settings between 10 and 30 volts.

Installing the Module

IMPORTANT

For a 12V dc encoder signal, use the 24V dc jumper
setting.

ATTENTION

!

If jumpers are not set to match the encoder type, the
module may be damaged.

5V dc

4.2-12V dc

24V dc

10-30V dc

JP6 (Z2)

JP5 (B2)

JP4 (A2)

JP3 (Z1)

JP2 (B1)

JP1 (A1 )

(default)

Jumper Settings

ATTENTION

!

Disconnect power before attempting to install,
remove, or wire the module.