Publication 1746-UM002B-EN-P - August 2004
Installation and Wiring 3-3
Figure 3.1 Jumper Settings
The 5V dc settings respond to inputs with an active voltage between
4.2 and 12 volts. The 24V dc settings respond to inputs with active or
high settings between 10 and 30 volts.
Installing the Module
IMPORTANT
For a 12V dc encoder signal, use the 24V dc jumper
setting.
ATTENTION
!
If jumpers are not set to match the encoder type, the
module may be damaged.
5V dc
4.2-12V dc
24V dc
10-30V dc
JP6 (Z2)
JP5 (B2)
JP4 (A2)
JP3 (Z1)
JP2 (B1)
JP1 (A1 )
(default)
Jumper Settings
ATTENTION
!
Disconnect power before attempting to install,
remove, or wire the module.