Counter control block, Counter control block -23 – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual

Page 73

Advertising
background image

Publication 1746-UM002B-EN-P - August 2004

Configuration and Programming 4-23

Output State on page 4-27 for a description of how the bytes are
combined.

If the start value is less than the stop value, the output state is applied
when the count or rate is within the range specified by the two values.
(For example, see ranges 1 through 3 on page 2-13.) If the start value
is greater than the stop value, the output state is applied when the
count or rate is outside the range. (For example, see range 4 on
page 2-13.) At least one of these bits must be set when programming a
range or a programming error is generated.

Counter Control Block

Figure 4.9 shows the format of the Counter Control programming
block. This block allows you to change the state of the following
counter controls for all four counters in one cycle:

• Enable/Disable Counter
• Soft Preset (if enabled)
• Internal Direction (if enabled)
• Output ON Mask
• Output Enable Mask
• Count or Rate Value (Class 1 only)
• Enable/Disable Range

All counters can be running when this block is sent to the module.

Figure 4.9 Counter Control Block Format

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Word 0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

Word 1

P1

0

0

0

0

0

0

C/R

1

0

0

0

0

0

ID1

SP1

EN1

Word 2

P2

0

0

0

0

0

0

C/R

2

0

0

0

0

0

ID2

SP2

EN2

Word 3

P3

0

0

0

0

0

0

C/R

3

0

0

0

0

0

ID3

SP3

EN3

Word 4

P4

0

0

0

0

0

0

C/R

4

0

0

0

0

0

ID4

SP4

EN4

Word 5

Output Enable Mask

Output ON (OR) Mask

Word 6

Enable Ranges

Word 7

RESERVED: Must Equal Zero