1734-8cfgdlx, Modes of usage, Standard point i/o module – Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual

Page 12

Advertising
background image

Publication 1734-UM015A-EN-E - November 2009

10 Introduction

1734-8CFGDLX

This module is an 8-point 24V DC I/O module with 8 self-configuring points
and DeviceLogix capabilities. Each of the I/O points can be either a DC input
or output. The module supports removal and insertion under power,
auto-address, and auto-baud in compliance with the POINTBus backplane.

1738-8CFGDLXM8, 1738-8CFGDLXM12, and 1738-8CFGDLXM23

The ArmorPOINT I/O family consists of modular I/O modules. The sealed
IP67 housing of these modules requires no enclosure. Note that
environmental requirements other than IP67 may require an additional
appropriate housing. I/O connectors are sealed M8 (pico), M12 (micro) or
M23 styles. The mounting base ships with the module.

Modes of Usage

The module can be used in one of the following modes:

as a standard POINT I/O module,

in a stand alone DeviceLogix program where it controls its own I/O,
and

in network applications with or without the peer exchange of data.

Standard POINT I/O Module

The module can simply be used as an 8-point configurable POINT I/O
module. It uses ODVA pre-defined Produce and Consume assemblies. Default
settings help to facilitate quick setup right out-of-the-box. It is CIP network
independent and it can run on DeviceNet, EtherNet/IP or ControlNet when
used in conjunction with an adapter.

Advertising