Status indicators of point i/o module, 1734-8cfgdlx module, Module status – Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual
Page 86

Publication 1734-UM015A-EN-E - November 2009
84 Troubleshooting
Status Indicators of POINT
I/O Module
See the figure and tables that show how to interpret the status indicators.
1734-8CFGDLX Module
Module Status
Indication
Probable Cause
Recommended Action
Off
No power applied to device.
Apply power to device.
Green
Device operating normally.
None.
Flashing
green
Device needs commissioning due to
missing, incomplete or incorrect
configuration.
Configure device properly.
Flashing red
Recoverable fault.
1. Cycle power to device.
2. If condition persists, replace
device.
Red
Unrecoverable fault may require
device replacement.
Replace device.
Flashing
red/green
Device is in self-test.
None.
1
3
0
2
Module
Status
Network
Status
Device
Logix
Status
1734
8CFGDLX
1
3
0
2
5
7
4
6
NODE:
44759
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
Status of I/O 4
Status of I/O 5
Status of I/O 6
Status of I/O 7
Module Status
Network Status
DeviceLogix Status