Spacing requirements – Rockwell Automation 1756-xxxx ControlLogix Chassis and Power Supplies Installation Instructions User Manual

Page 16

Advertising
background image

16

Rockwell Automation Publication 1756-IN005C-EN-P - March 2014

Chapter 1

Install Chassis and Power Supplies

Spacing Requirements

Use the following information to plan your installation.

Dimensions are in cm (in.).

IMPORTANT

Make sure you meet the minimum spacing requirements specified.

Allow 15.3 cm (6.0 in.) between chassis and a heat source, and allow
5.1 cm (2.0 in.) between a wireway and the top or bottom of a chassis.

Chassis are intended to be mounted only horizontally. Do not mount vertically.

W

i

r

e

w

a

y

Wireway

W

i

r

e

w

a

y

45796

15.3 (6.0)

10.2
(4.0)

7.7
(3.0)

5.1 (2.0)

15.3 (6.0)

5.1 (2.0)

15.3 (6.0)

10.2
(4.0)

The 10.2 (4.0)
measurement to the side
of the enclosure can
include the wireway.

Table 4 - Spacing Requirements, Top and Bottom

From a chassis to a

Requires this space, min

Cabinet

15.3 cm (6.0 in.)

Chassis or other heat source

15.3 cm (6.0 in.)

Wireway

5.1 cm (2.0 in.)

Table 5 - Spacing Requirements, Sides

From a chassis to a

Requires this space, min

Cabinet

10.2 cm (4.0 in.)

Chassis or other heat source

7.7 cm (3.0 in.)

Wireway

No minimum spacing required