Mounting dimensions – Rockwell Automation 1756-xxxx ControlLogix Chassis and Power Supplies Installation Instructions User Manual

Page 37

Advertising
background image

Rockwell Automation Publication 1756-IN005C-EN-P - March 2014

37

Install Chassis and Redundant Power Supplies

Chapter 2

Mounting Dimensions

Use these dimensions to plan your chassis installation.

Dimensions are in cm (in.).

Figure 19 - Redundant Power Supplies

Chassis or other heat source

7.7 cm (3.0 in.), 12.7 cm (5.0 in.) (only left
side)

7.7 cm (3.0 in.)

Redundant power supply

7.7 cm (3.0 in.), 12.7 cm (5.0 in.) (only left
side)

2.55 cm (1.0 in.)

Wireway

No minimum spacing required, 12.7 cm
(5.0 in.) (only left side)

No minimum spacing required

Table 9 - Spacing Requirements, Sides

From a

To a chassis
requires this space, min

To a redundant power supply
requires this space, min

1.1
(0.433)

0.55
(0.217)

Top Mounting
Hole Diameter

Bottom Mounting
Hole Diameter

17.5
(6.88)

14.4
(5.66)

42668

45829

15.8
(6.22)

7.0
(2.76)