Install Chassis and Power Supplies

Chapter 1

Connect the Protective Earth Ground

Use 2.1 mm2 (14 AWG) solid or stranded-copper wire rated at 90 °C (194 °F) or
greater to connect the protective earth ground. Tighten the nuts on the
protective earth ground terminal stud to a torque of 16.27 N•m (12 lb•in).

Connect the functional earth ground as shown in

Figure 13

.

Figure 13 - Protective Earth Ground Connection

+

-

+

-

45802

5

3

4

1

3

2

3

To Ground Bus

IMPORTANT

Some chassis can have a second protective earth-ground terminal stud. If your
application requires the use of a second protective earth-ground terminal stud,
please use the additional protective earth-ground terminal stud to connect the
chassis to the ground bus.

Item

Description

1

Protective earth-ground terminal stud

2

Star washer

3

Equipment grounding conductor (ground lug with 2.1 mm² [14 AWG] solid or stranded-copper wire rated
at 90 °C [194 °F] or greater)

4

Nut with captive star washer

5

Wiring terminal block (bottom terminal is protective earth ground)