Remove or Replace a
Redundant Power Supply

Use this information to remove or replace a redundant power supply.

Remove a Redundant Power Supply

Follow these steps to remove the redundant power supply.

1. Turn the redundant power supply OFF.
2. Disconnect the line power source voltage from the redundant power

supply and annunciator.

3. Remove the wiring terminal blocks.
4. Unscrew and disconnect the 1756-CPR2 cable.
5. Remove the bottom mounting screws.
6. Loosen the top mounting screws and slide the supply up and off the

mounting screws.

Replace a Redundant Power Supply

Follow the steps below to replace a redundant power supply.

1. Slide the redundant power supply over the top mounting screws and

tighten them.

2. Install the bottom mounting screws.
3. Connect the 1756-CPR2 cable.
4. Install the wiring terminal blocks.
5. Connect the line power source voltage to the redundant power supply and

annunciator.

6. Turn the redundant power supply ON.

When you turn ON the replacement redundant power supply, the
connected chassis automatically draws power from both redundant power
supplies.

WARNING: Remove or replace power supplies only when backplane and power
supply power are removed or the area is known to be nonhazardous. Removal
or replacement of a power supply in a hazardous area can cause an electrical arc
across the contacts if backplane power is still applied.

IMPORTANT

You can replace one redundant power supply while the other supply is
operating in nonredundant mode without affecting chassis operation.