Connect the grounding conductors to the ground bus, Connect ground bus to grounding-electrode system – Rockwell Automation 1756-xxxx ControlLogix Chassis and Power Supplies Installation Instructions User Manual

Page 26

Advertising
background image

26

Rockwell Automation Publication 1756-IN005C-EN-P - March 2014

Chapter 1

Install Chassis and Power Supplies

Connect the Grounding Conductors to the Ground Bus

Connect the equipment grounding conductors (functional and protective
earth ground) directly from each chassis to an individual bolt on the ground bus.

Figure 14 - Ground Bus Connection

Connect Ground Bus to Grounding-electrode System

Use a grounding-electrode conductor to connect the ground bus to the
grounding-electrode system.

At minimum, use 8.3 mm2 (8 AWG) solid or stranded-copper wire rated at
90 °C (194 °F) or greater for the grounding-electrode conductor to guard against
EMI. The National Electrical Code specifies safety requirements for the
grounding-electrode conductor.

Figure 15 - Grounding-electrode System Connection

Item

Description

1

Flat or star washer

2

Bolt

3

Equipment grounding conductor (from protective and functional earth ground connections)

4

Ground bus

5

Ground bus mounting

Item

Description

1

Flat or star washer

2

Bolt

3

Equipment grounding conductor (ground lug with minimum 8.3 mm² [8 AWG] solid or stranded-
copper wire rated at 90 °C [194 °F] or greater)

2

3

4

1

5

45803

2

3

1

45803

Advertising