Install the redundant power supplies – Rockwell Automation 1756-xxxx ControlLogix Chassis and Power Supplies Installation Instructions User Manual

Page 44

Advertising
background image

44

Rockwell Automation Publication 1756-IN005C-EN-P - March 2014

Chapter 2

Install Chassis and Redundant Power Supplies

Install the Redundant Power
Supplies

Follow these steps to install your redundant power supplies.

1. Drill holes in the back panel of the enclosure for the redundant power

supply.

See the

Spacing Requirements on page 35

for assistance in hole placement.

2. Insert the #10 Phillips screws into the top mounting holes, but do not

tighten completely.

3. Slide the redundant power supply over the installed screws and tighten the

screws.

4. Insert the bottom screws and tighten them.
5. Repeat these steps for additional power supplies.

ATTENTION: Do not drill holes for a redundant power supply above installed
equipment. Metal chips from drilling can damage the backplane and cause
intermittent operation.