Rockwell Automation Publication 1756-IN005C-EN-P - March 2014

Chapter 1

Install Chassis and Power Supplies

Install a Central Ground Bus

Each enclosure must contain a central ground bus. The ground bus is the
common connection for each chassis within the enclosure and the enclosure
itself.

For more information on installing a central ground bus, refer to the Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Connect the Functional Earth Ground on the Chassis

Use 8.3 mm2 (8 AWG) solid or stranded-copper wire rated at 90 °C (194 °F) or
greater to connect the functional earth ground.

Connect the functional earth ground as shown in

Figure 12

.

Figure 12 - Functional Earth Ground Connection

Item

Description

1

Chassis mounting tab

2

Equipment grounding conductor (ground lug with 8.3 mm² [8 AWG] solid or
stranded-copper wire rated at 90 °C [194 °F] or greater)

3

M4 or M5 (#10 or #12) flat or star washer

4

M4 or M5 (#10 or #12) Phillips screw and flat or star washer (or SEM screw)

20291-M

1

3

4

2