Install Chassis and Redundant Power Supplies

Chapter 2

Ground the Chassis

Complete these steps to properly ground your system.

Figure 30

shows an example grounding configuration. After you complete the

grounding steps, your system looks similar to this figure.

Figure 30 - Grounding Configuration Example

Use these guidelines when connecting the grounding:

Use a steel enclosure to guard against electromagnetic interference (EMI).
Install a bonding wire for electrical contact between the enclosure door

and the enclosure; do not rely on the hinge.

Make sure the enclosure-door viewing window is a laminated screen or a

conductive optical substrate (to block EMI).

Grounding Step

Page

Install a Central Ground Bus

46

Connect the Functional Earth Ground on the Chassis

46

Connect the Protective Earth Ground on the Chassis and
Redundant Power Supply

47

Connect the Grounding Conductors to the Ground Bus

48

Connect Ground Bus to Grounding-electrode System

48

TIP

To minimize the resistance between the chassis and ground connection, keep
wire lengths as short as possible.

Functional Earth Ground,

page 46

Protective Earth
Ground,

page 47

Cabinet

To Grounding-electrode System

45836

Ground Bus

8.3 mm² (8 AWG) solid
or stranded-copper
wire rated at 90 °C
(194 °F) or greater

2.1 mm² (14 AWG) solid
or stranded-copper
wire rated at 90 °C
(194 °F) or greater