Ground the chassis – Rockwell Automation 1756-xxxx ControlLogix Chassis and Power Supplies Installation Instructions User Manual

Page 23

Advertising
background image

Rockwell Automation Publication 1756-IN005C-EN-P - March 2014

23

Install Chassis and Power Supplies

Chapter 1

Ground the Chassis

Complete these steps to properly ground your chassis.

The following figure shows an example grounding configuration. After you
complete the grounding steps, your system looks similar to this figure.

Figure 11 - Grounding Configuration Example

Use these guidelines when connecting the grounding:

Use a steel enclosure to guard against electromagnetic interference (EMI).
Install a bonding wire for electrical contact between the enclosure door

and the enclosure; do not rely on the hinge.

Make sure the enclosure-door viewing window is a laminated screen or a

conductive optical substrate (to block EMI).

Grounding Step

Page

Install a Central Ground Bus

24

Connect the Functional Earth Ground on the Chassis

24

Connect the Protective Earth Ground

25

Connect the Grounding Conductors to the Ground Bus

26

Connect Ground Bus to Grounding-electrode System

26

TIP

To minimize the resistance between the chassis and ground connection, keep
wire lengths as short as possible.

Functional Earth Ground,

page 24

Protective
Earth Ground,

page 25

Cabinet

To Grounding-electrode System

45805

8.3 mm² (8 AWG) solid or
stranded-copper wire
rated at 90 °C (194 °F) or
greater

2.1 mm² (14 AWG) solid or
stranded-copper wire
rated at 90 °C (194 °F) or
greater

Ground Bus

Advertising