Replacing a dc/dc power supply – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual
Page 115

Rockwell Automation Publication 7000-UM151E-EN-P - January 2013
115
Component Definition and Maintenance Chapter 3
Replacing a DC/DC Power Supply
Figure 88 - Replacing a DC/DC power supply
1. With the drive energized, check that all output voltages are present (view
1).
2. De-energize the drive, isolate and lock out the control power, and remove
all wire connections from the unit (view 1).
3. Remove four (4) M6 (H.H.T.R.S.) so you can remove the DC/DC power
supply assembly from the low voltage panel (view 1).
4. Remove four (4) M4 (P.H.M.S.) and nylon shoulder washers from the
back of the mounting plate (view 2)
9
+5V_PWR (+5V,5A)
+5V,5A/com1
10
DGND (com1)
0V/com1
11
EARTH
earth ground
P4 – PWR (To
ACB)
PIN NO.
LABEL
DESCRIPTION ONLY
M4 (P.H.M.S.) and
nylon shoulder washer
Mounting Plate
Black Insulation
DC/DC
power supply
Part ID Label
M6 (H.H.T.R.S.)
VIEW “1”
VIEW “2”