Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual
Page 116

116
Rockwell Automation Publication 7000-UM151E-EN-P - January 2013
Chapter 3 Component Definition and Maintenance
5. Install the new DC/DC power supply. Ensure you replace the black
insulation between the DC/DC power supply and the mounting plate.
Repeat steps 4, 3, 2, 1 in this order to replace unit (view 2). E
6. Reconnect the P4 plug ground wire to the ground by the M10 bolt.
Take the following precaution when replacing printed circuit boards.
• Disconnect all drive power.
• Leave the replacement board in the anti-static bag until needed.
• Use an anti-static wrist strap, grounded in the low voltage control section.
There are no direct screw/terminal connections on any of the low voltage circuit
boards. All wire/terminal connections plug into the circuit boards. This means
that changing boards only requires the removal of the plugs, minimizing the
chance of mistakes when reconnecting all of the wiring.