Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control (PanelView 550) User Manual
Page 135

Rockwell Automation Publication 7000-UM151E-EN-P - January 2013
135
Component Definition and Maintenance Chapter 3
Figure 99 - Universal Encoder Board
Connections to the Universal Encoder Interface occur via a 1492-IFM20F
interface module. The connections to the IFM are detailed below.
Table 8 - Encoder Functions
Removed
Installed
Removed
Natural Binary Absolute Encoder Low True
Removed
Removed
Installed
Gray Code Absolute Encoder High True
Removed
Removed
Removed
Natural Binary Absolute Encoder High True
IFM Pin # Quadrature Encoder Function
Absolute Encoder Function
1
A1+
E0
2
A1-
E1
3
B1+
E2
4
B1-
E3
5
ENC_COM
ENC_COM
6
Z1+
E4
7
Z1-
E5
8
A2+ (Redundant or Dual ENC)
E6
9
A2- (Redundant or Dual ENC)
E7
10
ENC_COM
ENC_COM
11
B2+ (Redundant or Dual ENC)
E8
12
B2- (Redundant or Dual ENC)
E9
13
Z2+ (Redundant or Dual ENC)
E10
14
Z2- (Redundant or Dual ENC)
E11
15
ENC_COM
ENC_COM
16
ENC_COM
ENC_COM
17
ENC_COM
ENC_COM
ENC_TYPE
POL_QRDNT
CD_DQUAD
CONFIGURATION