General Reference Appendix A
Table 11 - PowerFlex Speed Regulation
Notes:
• Speed regulation is based on a percentage of motor synchronous speed.
• Tachometer to be mounted on the AC machine
• Operational 15 V DC Power Supply mounted in drive to power the
tachometer as a standard option with the tachometer feed back card.
• Customer is responsible for providing and mounting of tachometer
• Sleeve bearing motors require the tachometer to have an axial movement
tolerance.
• Recommended tachometers are shaft mounting type.
• Magneto resistive models are more adaptable to harsh environments.
• When installing, the tachometer body and electronics must be isolated
from ground (options available from the tachometer manufacturer to
accomplish this).
• There are usually limits on tachometer cable lengths. Ensure the maximum
length is suitable for the application.
Tachometer
Frequency Output
<6 Hz
6-15 Hz
>15 Hz
Without Tachometer
Not applicable
0.1%
0.1%
With Tachometer
0.02%
0.01%
0.01%
Recommended Tach PPR
Motor RPM
Tach ppr
3600
600
3000
600
1800
1024
1500
1024
1200
2048
1000
2048
900
2048
720
2048
600
2048