Chapter 2

Installation and Wiring

Using the 2090-K6CK-D44S0 Low-profile Connector Kit

The 2090-K6CK-D44S0 connector kit includes two motion-allowed jumpers.

Remove the jumpers to wire the safe torque-off connections. Install the jumper

when your application is not using the safe torque-off functionality, but your

application requires I/O connections.

The 2090-K6CK-D44S0 connector kit lets you cascade the safe torque-off

signals from drive-to-drive by using the 2090-CS0DSDS-AA

xx interface cable.

Figure 2 - Making 2090-K6CK-D44S0 Safety Connections

Refer to the Kinetix 6200 and Kinetix 6500 Modular Servo Drive User Manual,

publication

2094-UM002

, for other wiring examples using low-profile connector

kits.

IMPORTANT

You must remove the motion-allowed jumpers to wire the safe torque-off
connections.

P2

P1

P4

P3

P6

P5

P2

P1

P4

P3

P6

P5

40

42

39

39

41

40

0

40

44

39

39

43

40

14

25

17

26

18

15

0

0

27

28

19

20

23

24

21

22

27

28

19

20

23

24

21

22

14

25

17

26

18

15

0

0

40

42

39

39

41

40

0

40

44

39

39

43

40

S0

IN

S0

OUT

14
25
17
26
18
15
0
0

2090-K6CK-D44S0
Low-profile Connector Kit

Turn clamps over for smaller

diameter cables.

Motion-allowed Jumper Installation
(applies to 2094-

xx02x-M0x-S0

control modules)

Pin numbering corresponds to the IOD (44 pin)

connector. IOD-39 = P1-39 and P2-39.

Pins 39 and 40 are given multiple terminals to

accommodate connections for each of the inputs.

Refer to

page 18

for safety and

I/O signal descriptions.

Shrink-wrapped Insulation

Use shield clamps (2) to maximize contact with

cable shield for high-frequency bonding.

Use tie wraps (2) for stress relief.

I/O

Cable/Wires

Cascading S0

Safe-off Cables

Safety
Cable/Wires