Chapter 3

Safe Torque-off I/O Signals

Figure 8 - Safety Input Wiring Examples

Table 4 - IOD Connector Input Terminals

Short-circuits of the input loop to ground or 24V will be detected. For

dual-channel inputs, cross loops will also be detected.

Test_Out_0 (IOD-27)
Test_Out_1 (IOD-28)

Dual-channel

Equivalent

Safety Device

Light Curtain

or

Safety Mat

Drive

Drive

SS_IN_CH2 (IOD-23)
SS_IN_CH3 (IOD-24)

Test_Out_0 (IOD-27)
Test_Out_1 (IOD-28)

SS_IN_CH2 (IOD-23)
SS_IN_CH3 (IOD-24)

24VPWR (IOD-14)
24VCOM (IOD-15)

SPWR (IOD-17)

SPWR (IOD-17)

SCOM (IOD-18)

SCOM (IOD-18)

SS_IN_CH0 (IOD-19)
SS_IN_CH1 (IOD-20)

SS_IN_CH0 (IOD-19)
SS_IN_CH1 (IOD-20)

OSSD1
OSSD2

24V DC

24VPWR (IOD-14)
24VCOM (IOD-15)

IMPORTANT

Cross wiring of Test Outputs to Inputs is not allowed. For example, do not
connect TEST_OUT_0 to Input 1 or TEST_OUT_1 to Input 0.

Safe Stop Function

Signal

IOD Pin

Input 0 = Channel 0

SS_IN_CH0

IOD-19

Input 1 = Channel 1

SS_IN_CH1

IOD-20

Input 2 = Channel 2

SS_IN_CH2

IOD-23

Input 3 = Channel 3

SS_IN_CH2

IOD-24