Chapter 3

Safe Torque-off I/O Signals

Figure 10 - SS_Out to SS_In Connections for Multi-axis Applications

For more information on multi-axis configurations, see

Cascaded Configurations

starting on

page 27

.

Alternately, the first SS_Out output may be used to signal a programmable logic

controller (PLC) that a Safe Stop has been requested.

If the SS_In is ON (closed) and a successful Safe Stop Reset is performed, the

SS_Out output is turned ON.

If the Safe Stop is initiated or if a Safe Stop is initiated due to a fault, the SS_Out

output is turned OFF.

If an error is detected on either channel of the dual-channel output, a fault occurs,

which initiates the Category 0 Stop. The fault is latched until the drive is

successfully reset.

For more information on faults, refer to

Chapter 5

.

Drive 1

SS_OUT_CH0

SS_OUT_CH1

Drive 2

SS_IN_CH2

SS_IN_CH3

IOD-21

IOD-23

IOD-22

IOD-24