Rockwell Automation 6180W-xxxx VersaView Workstation User Manual User Manual

Page 60

Advertising
background image

Publication 6180W-UM001H-EN-P - August 2007

60 Specifications

Environmental Specifications

Attribute

Value

Temperature, operating

0…50 °C (32…122 °F)

Temperature, storage

-20…60 °C (-4…140 °F)

Relative humidity, operating

(1)

(1)

Derate above 40 °C to 45% at 50 °C.

20…85% without condensation

Relative humidity, nonoperating

(2)

(2)

Derate above 40 °C to 39% at 60 °C.

5…90% without condensation

Vibration, operating

0.006 in. p-p, (10…57 Hz); 1 g peak (57…500 Hz)

Vibration, nonoperating

0.012 in. p-p, (10…57 Hz); 2 g peak, (57…500 Hz)

Shock, operating

15 g (1/2 sine, 11 ms)

Shock, nonoperating

30 g (1/2 sine, 11 ms)

Enclosure ratings, panel mounted

NEMA Type 4, 12, IEC IP66

Certifications

(1)

(1)

See http://ab.com for declarations of conformity, certificates, and other certification details.

Attribute

Value

c-UL-us

UL 60950 recognized component, c-UL 950
recognized component, or UL/c-UL listed when
marked

CE

Marked for all applicative directives
LVD (72/23/EEC)
EMC (89/336/EEC)

C-Tick

Australian Radiocommunications Act, compliant
with: AS/NZS CISPR 11; Industrial Emissions

RoHS compliant