Installation & Hook-Up

19

Figure 2.9
Wiring an 846-SJxxxx-R2-x single resolver package to the Axis 0 Resolver

plug or the Axis 1 Resolver plug on the REC

Important: Anchor the cable so that no more than 2 feet of cable is

left unsupported. The excessive weight of an unanchored
cable could pull the plug out of the connector.

Connecting the Resolver to the Plug

After you have wired the resolver cable leads to the plugs, insert the
plugs in the resolver connectors on the REC. Figure 2.10 shows
where the resolver plugs connect to the REC.

Important: We designed and tested the REC to work with Allen–

Bradley resolver packages and cables up to 100 ft. If you
use longer cables, or cables other than those specified,
the product does not perform as specified.

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

845AB-CA-i-xx Cable

Green E
Black G

Red D
Black F

White A
Black B

Internal fault relay contact

Chassis Ground

Axis Fault
N.O.

Chassis Ground

846-SJABCD-R2-E
Resolver Assembly

Plug A

Plug B