Rockwell Automation 4100 REC Resolver to Encoder Converter Installation and Setup Manual User Manual
Page 28
Publication 999-126 - February 1996
Installation & Hook-Up
23
The relay output can be used to disable external devices or
incorporated into your machine’s E-stop string (or other protective
circuitry) for fail-safe protection. The REC provides Form_C
(Normally Open) contacts to disable external equipment in the event
of a malfunction.
Important: Both the fault relay and the LED (Axis OK) are
activated during normal operation and deactivated during
a malfunction.
The fault output relay contacts are UL listed and CSA certified for 1A
at 30V DC. Figures 2.13 and 2.14 are examples of typical fault relays.
Figure 2.13
A typical Normally Open Fault status contact
24V DC
11
1
CR1
CR1
Start/Stop String
Fault String
Start
REC Fault contact
located at Axis 0,1
Resolver connector
Stop
DC
Common