Installation & Hook-Up

Wiring the Drives Signal for a
Compact

When using the REC with an S Class Compact, the drive reference
signals (+/-10V) are passed from the Compact to the REC at
terminals 8, 9, and 10 on plug A (Axis 1), and at terminals 3, 4, and 5
on Plug B (Axis 0). To wire the drives signal:

1. Connect the drive signal to the servo amplifier using a twisted,

shielded cable (Belden 9501 or equivalent).

2. Wire the cable leads to the appropriate Power & Drives plugs ofr

the required axis. Figure 2.12 shows where to connect the drives
reference signals to the Power & Drives connector.

Both Axis 0 and Axis 1 can have drive signals present at their
connectors.

Note:

You do not need to wire the drive reference signal to the 1394
because it handles the reference signal output internally.

Figure 2.12
Wiring the Drive Reference Signal to an S Class Compact Motion Controller

Important: Anchor the cable so that no more than 2 feet of cable is

left unsupported. The excessive weight of an unanchored
cable could pull the plug out of the connector.

Connecting a Fault Relay

The REC is equipped with a fault detector that handles internal logic
voltage malfunctions and resolver phase loss faults. The fault detector
consists of:

An internal relay contact output that opens for each axis

An LED indicator that turns red for each axis

An encoder driver disabler for each axis

10

9

8

7

6

5

4

3

2

1

Ref +

Ref -

Servo

Amplifier

Axis 0

Ref +

Ref -

Servo

Amplifier

Axis 1

1 Reference +

1 Reference -

1 Reference Shield

0 Reference +

0 Reference -

0 Reference Shield

Plug A

Plug B